Requirements for protection against overload
Electrical
Requirements for protection against overload
Alex · 16 August 2018
This article will take a closer look at the conditions protective devices must meet to protect a conductor against overload.
The primary purpose of a protective device is to protect the circuit from damage, and for such purposes Regulation 433.1.1 requires the operating characteristics of a device protecting a conductor against overload to satisfy the following conditions:
Omission of overload protection devices
The omission of an overload protective device is permitted for both general and safety purposes. The installation of an overload protective device may not be needed for the general situations detailed in Regulation 433.3.1.
In addition, Regulation 433.3.3 permits the omission of overload protective devices for circuits supplying current using equipment where disconnection of the device could result in danger or damage. For example, the unexpected disconnection of the supply to the lifting magnet shown in Fig 2 would cause the unintended release of the object without warning.
Where overload protection is omitted provision of an overload alarm should be considered.
Source: https://www.voltimum.co.uk/articles/requirements-protection-against-overload
- In ≥ Ib - The rated current or current setting of the protective device (In) should not be less than the design current (Ib) of the circuit.
- In ≤ Iz - The rated current or current setting of the protective device (In) should not exceed the lowest of the current-carrying capacities (Iz) of any of the conductors of the circuit.
- I2 ≤ 1.45 Iz - The current (I2) causing effective operation of the protective device should not exceed 1.45 times the lowest current-carrying capacity (Iz) of any of the conductors of the circuit
Condition 1: In ≥ Ib
To avoid unwanted operation of the overload protective device when it is carrying the steady-state load current (Ib), condition 1 requires the rated current of the protective device (In) to be at least equal to Ib. However, due to the starting characteristics of the load, a higher value of In may be necessary for certain loads (Regulation 533.2.1 refers). In particular, certain types of electrical load such as discharge lighting, AC induction motors and transformers take a much higher current during starting than during normal operation. Consequently, a device protecting such a load must be carefully selected to ensure that it will not be operated by such ‘starting currents’. As shown in Table 1, circuit-breakers designed to BS EN 60898-1 are classified into three distinct types - B, C, and D - according to the magnitude of current required to achieve automatic disconnection.
Condition 2: In ≤ Iz
This condition is intended to give protection under normal load conditions such that the steady state temperature of the conductors will not exceed the maximum admissible value (such as 70₀C for thermoplastic insulated conductors). This is achieved by requiring the conductors to have sufficient current carrying capacity (Iz) to carry the rated current of the circuit protective device (ln).Condition 3: I2 ≤ 1.45 Iz
In circumstances when the circuit is subjected to an overload current, this condition is intended to ensure operation of the device within a time suitable to protect the insulation against damage from any high conductor temperatures caused by the overload current.

