Technical Guide: Cables installed in suspended ceilings
Electrical
Technical Guide: Cables installed in suspended ceilings
Alex · 13 February 2018
This article will take a closer look at the regulations and requirements associated with installing cables in suspended ceilings.
Suspended ceilings are often provided in commercial and similar premises. They generally consist of a grid of light metal bars, usually having an inverted ‘T’ section, into which ceiling tiles, recessed luminaires (light fittings) and ventilation grilles, for example, are installed (see Fig 1).
Surface-mounted luminaires, smoke detectors and similar items are sometimes installed to the underside of the ceiling. The void above a suspended ceiling, which accommodates the tension wires or other means by which the grid is suspended from the building structure, is commonly used for the routing of wiring systems and non-electrical services, such as pipework and ductwork.
Supporting of electrical cables
Some of the requirements applicable to cables in suspended ceilings are embodied in Regulation Groups 522.6, 522.7 and 522.8 of BS 7671. In particular, Regulations 522.8.4 and 522.8.5 call for cables to be supported, either continuously or at appropriate intervals, such that no damage or undue strain will occur to the cables themselves or to their terminations.
It is inadvisable for cables, including insulated and sheathed cables to BS 6004, to be laid directly on a suspended ceiling grid for a number of reasons, including:
Suspended ceilings are often provided in commercial and similar premises. They generally consist of a grid of light metal bars, usually having an inverted ‘T’ section, into which ceiling tiles, recessed luminaires (light fittings) and ventilation grilles, for example, are installed (see Fig 1).
Surface-mounted luminaires, smoke detectors and similar items are sometimes installed to the underside of the ceiling. The void above a suspended ceiling, which accommodates the tension wires or other means by which the grid is suspended from the building structure, is commonly used for the routing of wiring systems and non-electrical services, such as pipework and ductwork.
Supporting of electrical cables
Some of the requirements applicable to cables in suspended ceilings are embodied in Regulation Groups 522.6, 522.7 and 522.8 of BS 7671. In particular, Regulations 522.8.4 and 522.8.5 call for cables to be supported, either continuously or at appropriate intervals, such that no damage or undue strain will occur to the cables themselves or to their terminations.
It is inadvisable for cables, including insulated and sheathed cables to BS 6004, to be laid directly on a suspended ceiling grid for a number of reasons, including:
- The cables are liable to be damaged, both during installation and later, by the sharp edges of the grid (Regulations 522.6.201 and 522.8.1). For example, a cable may come into contact with the cut edges of the grid at a notch where sections of grid intersect, or may become trapped between a ceiling tile and the grid, possibly when other trades are carrying out work in connection with the ceiling or other services routed above.
- The suspended ceiling grid may not have been designed to take the additional weight of cables, and may deform or collapse as a result.
- Providing a conduit or trunking system, or cable tray (metallic or non-metallic), fixed at suitable spacings to the building structure above the ceiling, or to walls or other structural elements.
- Providing a catenary system as shown in Fig 2, to which the wiring system may be attached using proprietary clips, cable-ties or cable-hangers at appropriate intervals.
- Attaching the cables by suitable clips or cable ties to ceiling support rods.
- Flexible cord connections to luminaires should be as short as possible (ideally, a vertical drop from the fixed connection to the luminaire).
- Flexible cords should not be allowed to rest on top of, or come into contact with the sharp edges of the inverted ‘T’ section of the ceiling grid.
- Suitable cord grips should be provided to securely retain the sheath of the flexible cord if strain is likely to occur on terminations within a luminaire. For some types of luminaire, a cord grip may need to be purchased separately.